Performance Data



CONCORE BY TATE - OFFICES & EQUIPMENT ROOMS

Quick Quote

    Benefits:
  • Excellent rolling load performance
  • Interchangeable panel strengths
  • Epoxy finish for lifetime protection
  • Solid and quiet
  • Superior ultimate load performance
  • Completely non-combustible
  • Excellent grounding and electrical continuity
  • Flame spread and smoke development rating: Class A

ConCore® Performance Selection Chart

SYSTEM TYPE SYSTEM WEIGHT STATIC LOADS ROLLING LOADS IMPACT LOADS
Panel Understructure Concentrated
Loads
Uniform
Loads
Ultimate
Loads
10
passes
10,000
passes
ConCore 1250 Bolted Stringer 10.5 lbs/ft2
51 kg/m2
1250 lbs
567 kg
300 lbs
136 kg
3850 lbs
1746 kg
1000 lbs
454 kg
800 lbs
363 kg
150 lbs
68 kg
Posilock 9.5 lbs/ft2
46 kg/m2
1250 lbs
567 kg
300 lbs
136 kg
3750 lbs
1701 kg
1000 lbs
454 kg
800 lbs
363 kg
100 lbs
45 kg
ConCore 1500 Bolted Stringer 11.5 lbs/ft2
56 kg/m2
1500 lbs
680 kg
375 lbs
170 kg
5100 lbs
2313 kg
1250 lbs
567 kg
1000 lbs
454 kg
150 lbs
68 kg
Posilock
10.5 lbs/ft2
51 kg/m2
1500 lbs
680 kg
375 lbs
170 kg
4600 lbs
2087 kg
1250 lbs
567 kg
1000 lbs
454 kg
100 lbs
45 kg
ConCore 2000 Bolted Stringer
12.5 lbs/ft2
61 kg/m2
2000 lbs
907 kg
500 lbs
227 kg
6100 lbs
2767 kg
1500 lbs
680 kg
1250 lbs
567 kg
150 lbs
68 kg
ConCore 2500
Bolted Stringer
13.5 lbs/ft2
66 kg/m2
2500 lbs
1134 kg
625 lbs
284 kg
6900 lbs
3130 kg
1500 lbs
680 kg
2000 lbs
907 kg
150 lbs
68 kg
Note: Loads applied on a one square inch area. Results above indicate weakest point of panel.